Earthing stands as the backbone of electrical safety in any installation. If you don’t have a solid earth path with low resistance, faults can’t clear safely, and the risk of electric shock or fire just sticks around.
In the UK, you’ll run into three main earthing systems: TN-S, TN-C-S (also called PME), and TT. Each one works in its own way and comes with different rules for bonding, testing, and design.
Knowing your earthing system shapes everything from fault protection to whether you can run power to an outbuilding or add an EV charger.
This guide breaks down what the letters mean, how each system keeps you safe, and the key terms worth knowing.
You’ll get the basics on the main earthing terminal, protective conductors, bonding requirements, and when PME supplies come with restrictions.
Not Sure Which Earthing System Your Property Uses?
If you’re unsure whether your property runs a TN-S, TN-C-S, or TT earthing arrangement, Bains Electrical can test your installation and confirm the earthing type as part of a standard inspection. Call us on 0141 310 9801 to book.
The Main Earthing Systems Terminologies

TN‑S system: separate neutral and earth from the transformer’s earth terminal
In a TN-S setup, the neutral and protective earth wires stay separated all the way through. The earth connection starts at the transformer and runs independently to your installation, usually through a dedicated conductor or the cable’s metal sheath.
TN‑C‑S (PME) system: combined neutral and CPC in supply
TN‑C‑S is what you’ll find in most new UK homes. The electricity supplier brings a combined PEN conductor from the substation to your property.
Once inside, this splits into separate neutral and earth wires at the meter.
TT system: local earth electrode at the consumer
With a TT system, you’re in charge of your own earth electrode at your property. The electricity supplier earths their transformer, but they don’t give you an earth connection.
You’ll need to create your own earth using metal rods or plates buried in the ground.
IT system: isolated or high‑impedance neutral for specialised installations
The IT system skips a direct connection between neutral and earth. The neutral is either completely isolated or hooked up through high impedance.
Honestly, you won’t see this much in the UK. Hospitals and some industrial setups use IT systems where keeping the supply going is critical.
MET: Main Earthing Terminal
The MET is where all your protective conductors meet up in your installation. You’ll usually spot it near your consumer unit or meter box.
Your main earthing conductor from the supplier lands here. All main protective bonding conductors also tie in at this point, giving your property a single earthing reference.
Earthing Conductor
The earthing conductor links your installation’s exposed metal parts to the main earthing terminal. Look for the green and yellow stripes; it’s hard to miss.
BS 7671 sets the minimum sizes based on your live conductor. Bigger cables need chunkier earth wires to safely carry fault current.
CPC: Circuit Protective Conductor
The CPC runs alongside the live and neutral wires in your cables. It connects exposed metal parts of your electrical gear back to the earth terminal at your consumer unit.
This conductor gives fault current a low-resistance path and helps protective devices trip when needed.
PEN Conductor: Protective Earth and Neutral in One
A PEN conductor combines protective earth and neutral in a single wire. TN-C-S systems use this before the supply reaches your property.
Once inside, the PEN splits into a neutral and an earth conductor.
Earth Electrode
An earth electrode connects your installation directly to the ground. It’s a must-have in TT systems when the supplier skips the earth terminal.
Usually, it’s a copper or steel rod hammered into the soil.
Earth Electrode Resistance
If you’re running a TT system, you’ll need to measure your earth electrode’s resistance. This tells you how well your earth rod connects to the ground.
Aim for the lowest resistance you can get; most installations should be below 200 ohms.
Main Protective Bonding
Main protective bonding connects the extraneous-conductive-parts to your main earthing terminal. You’ll bond metal services like gas pipes, water pipes, and any structural steel as they enter the building.
This helps prevent dangerous voltages between earthwork and exposed metalwork during faults.
Supplementary Bonding in Bathrooms
Supplementary bonding links exposed metal bits in bathrooms to cut down shock risk. Taps, pipes, radiators, and metal baths all count.
Most modern UK bathrooms don’t need it if you’ve got 30 mA RCD protection on every circuit.
Equipotential Bonding
Equipotential bonding ties metalwork in your home to the main earthing terminal. Water pipes, gas pipes, and steel all get connected.
This bonding keeps everything at the same electrical potential during a fault, protecting you from shocks.
Touch Voltage
Touch voltage is what you might get exposed to if you touch a faulty appliance or metal part during an earth fault. Good earthing keeps this voltage safe by letting protective devices like MCBs or RCDs disconnect the supply fast.
Step Voltage
Step voltage pops up when current flows through the ground during a fault. You get a voltage difference between two points where your feet could be.
This can be risky during earth faults in any system. The voltage across the ground might send current through your body from one foot to the other.
SELV: Separated Extra Low Voltage
SELV circuits run at 50V AC or less and don’t connect to earth or other circuits. They’re separated from mains voltage by a safety isolating transformer.
You’ll see SELV in things like bathroom shaver sockets and low-voltage lighting. It relies on low voltage for protection, not earthing.
PELV: Protective Extra Low Voltage
PELV keeps the voltage to 50V AC or 120V DC and uses a safety isolating transformer to separate circuits from the earth.
The protective conductor connects exposed parts to earth, adding a layer of safety even at extra-low voltage.
What Is Earth Fault Loop Impedance?

Earth fault loop impedance is the total impedance of the path a fault current travels.
It runs from the point of fault, along the CPC to the main earthing terminal, through the earthing conductor and supply earth, then back to the transformer via the neutral. The lower the impedance, the higher the fault current, and the faster the protective device trips.
If you’re getting unexplained RCD trips or a tingling sensation from pipes and taps, the earthing arrangement itself may be at fault. Professional electrical fault finding can isolate the problem and determine whether the issue sits with the earth path, the bonding, or the consumer unit.
Ze: External Earth Fault Loop Impedance
Ze is the impedance of everything outside the installation, the supply network belonging to the DNO. It is measured at the origin, usually the consumer unit, with the installation’s earthing disconnected.
The DNO can also provide a declared maximum value, though a measured reading taken during inspection and testing gives a truer picture of the actual supply conditions on site.
Zs: Total Earth Fault Loop Impedance
Zs is the complete loop: Ze plus the resistance of the circuit conductors (R1 + R2). It is measured at the furthest point of each circuit, where impedance is highest. BS 7671 sets maximum Zs values for every protective device type and rating. Staying below these limits proves the device will disconnect the supply within the required time during an earth fault.
R1 + R2: The Circuit Conductor Contribution
R1 is the resistance of the line conductor; R2 is the resistance of the circuit protective conductor.
Both are measured together during the continuity test using a multifunction tester, with the line and CPC linked at the board. Adding the R1 + R2 reading to Ze gives the expected Zs, which can then be checked against the tables in BS 7671.
Maximum Disconnection Times Under BS 7671
On 230V circuits, final circuits rated up to 32A must disconnect within 0.4 seconds.
Fixed equipment and distribution circuits are allowed up to 5 seconds. On TT systems, the earth electrode resistance is usually far too high for an MCB to meet these times on its own, so an RCD is essential to achieve safe disconnection.
Frequently Asked Questions
What is the difference between TN-S, TN-C-S and TT earthing systems in the UK?
The big difference is how the earth path hooks back to the electricity supply.
With TN-S, your earth wire runs on its own from your place all the way back to the transformer. The Distribution Network Operator (DNO) gives you a dedicated earth terminal.
TN-C-S systems combine neutral and earth into one conductor in the supply network, which is PME (Protective Multiple Earthing). Inside your property, neutral and earth are split at your main earthing terminal.
What is the most common earthing system in Scottish properties?
TN-C-S (PME) is the go-to for new connections in Scotland.
Most new housing and upgraded properties use this system, since the DNO installs it by default. It’s reliable and cheaper to set up.
Some older homes might still have TN-S, especially if they predate PME. Rural places sometimes use TT, particularly where overhead lines are the norm.
How can you identify whether a property has TN-S, TN-C-S or TT earthing?
Check the supply cable and earthing setup at the meter.
A TN-S system uses a metal-sheathed supply cable, and the earth terminal connects to the metal sheath. You’ll see the metal covering acting as the earth.
TN-C-S systems usually have a black concentric cable, with the earth clamp attached to the cable sheath. The installation’s earth wire hooks up to the neutral terminal or a combined neutral-earth block from the DNO.
What is PME, and why does it restrict outbuilding earthing in Scotland?
PME stands for Protective Multiple Earthing, the technical name for TN-C-S, which is used all over the UK.
In PME, neutral and earth share a conductor in the supply network. The DNO earths this combined conductor at several points along the distribution system.
Scottish rules limit PME earthing for outbuildings, mostly for safety. If the supply neutral fails, it can reach a dangerous voltage.
That’s especially risky in outbuildings, where you might touch earthed metalwork and true earth (like soil or concrete floors) at the same time.
What is the difference between earthing and bonding?
Earthing and bonding handle different, though related, safety roles in your electrical installation.
With earthing, you connect exposed metal parts of electrical equipment to the main earthing terminal. That way, if a fault occurs, current can flow safely back to the supply.
This path helps fuses or circuit breakers shut off the circuit quickly when something goes wrong. It’s a direct safety measure, one that’s easy to overlook until you need it.
Bonding, on the other hand, links metallic parts that aren’t usually live. Main protective bonding connects things like water pipes, gas pipes, and structural metalwork to your main earthing terminal.